Trench Technology
Katherm QK nano
Article no.:
442170743141C1
Overview
- KaControl control system for operation via a separate room control unit, external control via a 0-10 V signal or building automation systems, such as KNX, modbus, BACnet (additional plug-in card accessory required)
- Room control of up to six units or up to 30 units with CANbus cards that are additionally required
- Demand-led automatic fan or optional manual fan control
- Connection options, including external room sensor, window contact etc.
- Individually parametrisable for optimum adaptation to the situation on site
The KaControl control option provides the option of omitting the valve control data point when externally controlled by an on-site 0-10 V signal. The fan valve and speed control logic comes from the KaControl. Note the deviation of the signal points from the design program with 0-10 V control by others.
Design program data: 2 V 4 V 6 V 8 V 10 V
External 0-10 V on the KaControl: 4.3 V 5.5 V 6.8 V 7.8 V 10 V
The Eurokonus valve connection enables the Katherm QK nano to be quickly and easily installed on site. In addition, height adjustment feet and raised floor height adjustment feet are supplied as standard to further reduce the installation time and thus the cost.
- 24 V electromechanical
- 230 V electromechanical including power unit and terminal block or KaControl incl. power unit, PCB and connection box
- For valves and electrical components
- With cover for visual protection and to protect against dirt
- Prevents damage to the convector when installing the valves or threaded connectors
- For the simple fixing of the floor trench
- With rubber underlay for acoustic decoupling
Calculate performance data
Sound power octave spectrum
The sound power is determined depending on the use according to DIN EN ISO 3741 (in the echo chamber), according to DIN EN ISO 3744 (in the low-reflective half-space) or according to DIN EN ISO 9614 (intensity method).
Oktave Spektrum
EPD data
Item number-specific LCA data based on verified EPD according to EN 15804, which is available for download at The International EPD System. Separate subdivision of life cycle modules available online via button "EPD data sheet". The environmental impacts of module B refer to 1 year of operation. A: Product and construction process stage - B: Use stage - C: End of life stage - D: Benefits and loads beyond the system boundary
A | B | C | D | |
---|---|---|---|---|
GWP - Total kg CO2 eq | 7.11E+01 | 5.61E+00 | 3.73E+00 | -3.16E+01 |
GWP - fossil kg CO2 eq | 7.06E+01 | 5.58E+00 | 3.73E+00 | -3.13E+01 |
GWP - Biogenic kg CO2 eq | 2.52E-01 | 7.98E-03 | 4.70E-04 | -5.19E-02 |
GWP - Luluc kg CO2 eq | 2.58E-01 | 3.25E-02 | 2.95E-04 | -1.72E-01 |
ODP kg CFC-11 eq | 1.98E-06 | 2.45E-07 | 6.76E-08 | -7.99E-07 |
AP mol H+ eq | 8.28E-01 | 5.93E-02 | 1.68E-03 | -4.89E-01 |
EP - fresh water kg P eq | 6.78E-02 | 4.35E-03 | 7.63E-05 | -4.08E-02 |
EP - marine kg P eq | 1.58E-01 | 1.34E-02 | 5.71E-04 | -4.10E-02 |
EP - country mol N eq | 9.96E-01 | 7.35E-02 | 5.84E-03 | -4.88E-01 |
POCP kg NMVOC | 3.72E-01 | 2.15E-02 | 1.89E-03 | -1.94E-01 |
ADPE kg Sb eq | 7.30E-03 | 6.15E-04 | 1.40E-06 | -5.02E-03 |
ADPF MJ | 9.16E+02 | 1.28E+02 | 3.96E+00 | -3.83E+02 |
WDP m³ depriv. | 1.86E+01 | 9.41E-01 | 1.60E-01 | -7.08E+00 |
GWP-GHG kg CO2 eq | 7.12E+01 | 5.63E+00 | 3.73E+00 | -3.16E+01 |
PM disease inc. | 5.82E-06 | 2.25E-07 | 2.49E-08 | -2.56E-06 |
IR kBq U-235 eq | 7.34E+00 | 4.08E+00 | 1.83E-02 | -2.57E+00 |
ETP - FW CTUe | 1.08E+03 | 1.04E+02 | 2.87E+01 | -5.45E+02 |
HTP - C CTUh | 3.80E-07 | 1.14E-08 | 6.12E-10 | -1.73E-07 |
HTP - NC CTUh | 7.85E-06 | 6.31E-07 | 6.90E-09 | -5.32E-06 |
SQP - | 5.97E+02 | 7.05E+01 | 4.01E+00 | -1.63E+02 |
PERE MJ | 1.78E+02 | 2.90E+01 | 2.28E-01 | -6.17E+01 |
PERM MJ | 0.00E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
PERT MJ | 1.78E+02 | 2.90E+01 | 2.28E-01 | -6.17E+01 |
PENRE MJ | 9.16E+02 | 1.28E+02 | 3.96E+00 | -3.83E+02 |
PENRM MJ | 0.00E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
PENRT MJ | 9.16E+02 | 1.28E+02 | 3.96E+00 | -3.83E+02 |
SM kg | 0.00E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
RSF MJ | 0.00E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
NRSF MJ | 0.00E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
FW m³ | 6.65E-01 | 6.88E-02 | 4.12E-03 | -2.44E-01 |
HWD kg | 0.00E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
NHWD kg | 3.89E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
RWD kg | 0.00E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
CRU kg | 0.00E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
MFR kg | 0.00E+00 | 0.00E+00 | 1.20E+01 | 0.00E+00 |
MER kg | 0.00E+00 | 0.00E+00 | 1.42E+00 | 0.00E+00 |
EE (Electrical) MJ | 0.00E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
EE (Thermal) MJ | 0.00E+00 | 0.00E+00 | 0.00E+00 | 0.00E+00 |
Accessories
Control accessories KaControl
KaController
with one-button operation, 24 V, wall-mounted room control unit, with integral room temperature sensor, Protection class IP 30, Temperature setting range 8 - 35 °C, Colour similar to RAL 9010 pure white, made of resistant PVC, Type 3210001
Suitable for: All units with control configuration KaControl C1
Suitable for: All units with control configuration KaControl C1
Article no.:
196003210001
KaController
with one-button operation, 24 V, wall-mounted room control unit, with integral room temperature sensor, Protection class IP 30, Temperature setting range 8 - 35 °C, Colour similar to RAL 9017 traffic black, made of resistant PVC, Type 3210006
Suitable for: All units with control configuration KaControl C1
Suitable for: All units with control configuration KaControl C1
Article no.:
196003210006
KaController
with side operating keys, 24 V, wall-mounted room control unit, with integral room temperature sensor, Protection class IP 30, Temperature setting range 8 - 35 °C, Colour similar to RAL 9010 pure white, made of resistant PVC, Type 3210002
Suitable for: All units with control configuration KaControl C1
Suitable for: All units with control configuration KaControl C1
Article no.:
196003210002
room temperature sensor
Wall-mounted, Surface-mounted, Protection class IP 30, Colour similar to RAL 9010 pure white, made of plastic, Type 3250110
Is the KaController installation site suitable for a temperature measurement? - If it is not suitable, e.g. behind a curtain, then a KaControl room temperature sensor should be chosen for each group!
Suitable for: all units with KaControl -C1 and climate controller art. no. 19600014894*
Is the KaController installation site suitable for a temperature measurement? - If it is not suitable, e.g. behind a curtain, then a KaControl room temperature sensor should be chosen for each group!
Suitable for: all units with KaControl -C1 and climate controller art. no. 19600014894*
Article no.:
196003250110
KaControl Tableau SEL4.0
with touch terminal, to monitor and control up to 60 Kampmann secondary air units (maximum 25 groups, maximum 6 units per group), 230 V AC, 30 W, Wall-mounted, Protection class IP 54, Colour RAL 7035 grey, Type 3232223
Suitable for: All units with control configuration KaControl C1 in conjunction with Modbus card Typ3260101
Suitable for: All units with control configuration KaControl C1 in conjunction with Modbus card Typ3260101
Article no.:
196003232223
Serial KNX card
for integration into a KNX/EIB network, interface PCOS00KXN0, Type 3260702
The communication card slots into the free interface on the PCB.
Suitable for: All units with control configuration KaControl C1
The communication card slots into the free interface on the PCB.
Suitable for: All units with control configuration KaControl C1
Article no.:
196003260702
Serial CANbus card
to increase the number of units in a single-circuit system from 7 to a maximum of 30 units, one required per unit, Extension of the cable length from the first to the last unit from 30 m to 500 m, Can only be used with the KaControl -C1 control version!The room temperature cannot be recorded by a room sensor when using CanBus cards., Type 3260301
Suitable for: All units with control configuration KaControl C1
Suitable for: All units with control configuration KaControl C1
Article no.:
196003260301
Serial Modbus card
Type 3260101
Required for each device for connection to KaControl panels or on-site Modbus networks.
The communication card slots into the free interface on the PCB.
Suitable for: All units with control configuration KaControl C1
Required for each device for connection to KaControl panels or on-site Modbus networks.
The communication card slots into the free interface on the PCB.
Suitable for: All units with control configuration KaControl C1
Article no.:
196003260101
KaControl visualisation
for the central monitoring and control of air handling units, Type 3210701
The KaControl visualisation unit is used to monitor and control individual control zones and secondary air units for 4-pipe heating/cooling, 2-pipe heating or 2-pipe cooling.
The central interface for monitoring Kampmann products provides optimum assistance with technical monitoring.
Suitable for: All units with control configuration KaControl C1 in conjunction with Modbus card Typ3260101, 100 Units
The KaControl visualisation unit is used to monitor and control individual control zones and secondary air units for 4-pipe heating/cooling, 2-pipe heating or 2-pipe cooling.
The central interface for monitoring Kampmann products provides optimum assistance with technical monitoring.
Suitable for: All units with control configuration KaControl C1 in conjunction with Modbus card Typ3260101, 100 Units
Article no.:
196003210701
KaControl visualisation
for the central monitoring and control of air handling units, Type 3210702
The KaControl visualisation unit is used to monitor and control individual control zones and secondary air units for 4-pipe heating/cooling, 2-pipe heating or 2-pipe cooling.
The central interface for monitoring Kampmann products provides optimum assistance with technical monitoring.
Suitable for: All units with control configuration KaControl C1 in conjunction with Modbus card Typ3260101, 300 Units
The KaControl visualisation unit is used to monitor and control individual control zones and secondary air units for 4-pipe heating/cooling, 2-pipe heating or 2-pipe cooling.
The central interface for monitoring Kampmann products provides optimum assistance with technical monitoring.
Suitable for: All units with control configuration KaControl C1 in conjunction with Modbus card Typ3260101, 300 Units
Article no.:
196003210702
Valve kits
Valve kit
Includes 1x pre-settable axial valve, 1x return shut-off valve, straight, matching spacer, Max. operating pressure 10 bar
Suitable for: Katherm QK nano Trench Technology, DN 15
Suitable for: Katherm QK nano Trench Technology, DN 15
Article no.:
194000442110
Valve actuators, supplied loose
Valve actuator kit
Drive T, 24 V AC/DC, 2-point, normally closed, 0.5m connecting line-AEH, PVC, VA10N, 1 W, Protection class III, Protection class IP 54, Cable length 0.12 m, supplied separately, made of Polyamide
Suitable for: All units with electro-mechanical control configuration KaControl C1 in conjunction with 2-way valve or differential pressure-independent valve
Suitable for: All units with electro-mechanical control configuration KaControl C1 in conjunction with 2-way valve or differential pressure-independent valve
Article no.:
1960TS0P04050010B
Connection accessories
Connection set
with two return shut-off valves and matching adapter; when using the Katherm QK nano with a central manifold
Suitable for: Katherm QK nano
Suitable for: Katherm QK nano
Article no.:
194000442101
Valves and return shut-off valves
Pre-adjustable valve kit
Axial, pre-settable, Connection 1/2'', Max. operating pressure 10 bar
Suitable for: Katherm NK 137/182, Katherm QK, Katherm HK, Katherm HK, DN 15
Suitable for: Katherm NK 137/182, Katherm QK, Katherm HK, Katherm HK, DN 15
Article no.:
194000346911
Return shut-off valve
Straight, Connection 1/2''
Suitable for: Katherm NK, Katherm QK or Katherm HK
Suitable for: Katherm NK, Katherm QK or Katherm HK
Article no.:
194000145952
Differential pressure-independent valve kit
Connection 1/2'', Max. operating pressure 10 bar, supplied separately
Suitable for: DN 15
Suitable for: DN 15
Article no.:
194000347914
Installation covers
Installation cover
to protect trench during installation, factory-fitted, grilles are packed separately
price per m
Suitable for: Katherm QK nano
price per m
Suitable for: Katherm QK nano
Article no.:
194000101916
Downloads
Declarations/Certificates
Certificate ISO 50001:2018
PDF
(194 kB)
Certificate ISO 9001:2008
PDF
(118 kB)
Digital EPD database Katherm QK nano
EPD Katherm QK nano
PDF
(9.3 MB)
UKCA Declaration Katherm HK, QK, QK nano
PDF
(468 kB)
Cross-product information
Products
PDF
(10.7 MB)
Information sheet trench heating BS EN 16430 UK version
PDF
(215 kB)
Technical catalogues
KaControl MC - Multi Connect
PDF
(2.2 MB)
Katherm QK, QK nano trench heating
PDF
(12.7 MB)
Manuals
KaControl MC - Multi Connect
PDF
(1.3 MB)
Katherm QK nano trench heating
PDF
(9.7 MB)
BIM data (Building Information Modeling)
Kampmann Group BIM data
Installation plans
Katherm QK nano, KaControl version
PDF
(801 kB)
CAD-Drawings
Katherm QK nano, trench length 2300 mm, electromechanical control or KaControl, cross-sections, views
PDF
(125 kB)
Katherm QK nano, trench length 2300 mm, electromechanical control or KaControl, cross-sections, views
DWG
(434 kB)
Katherm QK nano, trench length 2300 mm, electromechanical control or KaControl, cross-sections, views
DXF
(1.7 MB)